Skip to content

CVE-2016-8562

Siemens SIMATIC CP 1543-1 Improper Privilege Management Vulnerability

  • Actively exploited
  • High · 7.5 of 10
Exploited since
3 Mar 2022
added to the CISA list
Chance of attacks
3.6%
in the next 30 days (FIRST EPSS)
Fix deadline
24 Mar 2022
for US federal agencies
Published
18 Nov 2016
in the NVD

What this means

An improper privilege management vulnerability exists within the Siemens SIMATIC Communication Processor (CP) that allows a privileged attacker to remotely cause a denial of service.

CISA

A vulnerability has been identified in SIMATIC CP 1543-1 (All versions < V2.0.28), SIPLUS NET CP 1543-1 (All versions < V2.0.28). Under special conditions it was possible to write SNMP variables on port 161/udp which should be read-only and should only be configured with TIA-Portal. A write to these variables could reduce the availability or cause a denial-of-service.

NIST National Vulnerability Database

What to do

Apply updates per vendor instructions.

CISA's required action. If you use the product, install the vendor's update as soon as possible.

Affected

  • n/a n/a

Official sources

Data from the NIST National Vulnerability Database, the CISA Known Exploited Vulnerabilities list, FIRST EPSS and ENISA, checked 18 Nov 2026. CVSS vector CVSS:3.1/AV:N/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H.

May we count your visit with Google Analytics? It sets cookies only if you accept. Privacy Policy